SOL-812 T1+T2 1/1 RCD 3F 16 A T2 prefabricated AC/DC switchboard Iontec
SOL-812 DC T1+T2 1/1 AC RDC 3F 16 A T2 switchgear - 1 MPPT - surge arrester 1200 V
260.25excl. VAT
260.25 € incl. VATThe ACDC T1+T2/T2 electrical switchgear provides full protection of AC and DC circuits of a photovoltaic installation from the effects of surges. Its design is suitable for surface mounting.
The product consists of a housing, transparent door, TH-35 mm rails, N+PE terminals, front cover with cut-outs for apparatus, chokes, caps, and mounting parts.
Electrical and mechanical parameters of the enclosure:
- Designed for surface mounting
- Manufactured in accordance with EN 60670, EN 62208
- Rated current In 63 A
- IP65 rating
- Protection class II
- Rated insulation voltage Ui: 690 V AC, 1000 V DC
- Glow wire test: 650°C
- Impact resistance: IK08
- Operating temperature: -25°C to +60°C
- Halogen-free recyclable plastic
Overcurrent circuit breaker NOARK Ex9BN 3P:
- B curve
- Manufactured in accordance with IEC/EN 60898-1
- Rated short-circuit breaking capacity ICN: 6 kA
- Rated switching voltage 230/400 V AC
DC DEHN Combo 1200 V typ 1+2 surge protector:
- PV T1+T2 (Class I+II, Type 1+2, B+C)
- To be used in accordance with the standard: PN-HD 60364-7-712
- Rated discharge current In: 20 kA (8/20 μs)
- Voltage protection level: 3.8 kV
- Size: 4 modules
- Maximum PV voltage Ucpv: 1200 V
- Tripping time tA 25 ns
- Optional auxiliary contact to indicate insert status
AC surge arrester NOARK Ex9UE2 20 4P 275:
- T2 (Class II, Type 2, C)
- Rated discharge current In (8/20 us) per phase: 20 kA
- Continuous operating voltage Uc: 275 V per phase
- Size: 4 modules
Residual-current circuit breaker Ex9L-N:
- Switch type: A
- Rated current: 40 A
- Rated residual current: 100 mA
- Number of poles: 4
- Short-circuit withstand capacity: 6 kA
SOL-812
Attributes
- Switchgear type
- Prefabricated
- Type of protection
- DC/AC
- Max. voltage [V]
- 1000
- Max. current [A]
- 16
- Feed-in phases
- 3
- Number of MPPT inputs
- 1
- Switchboards
- 24-pole
- Dimensions [mm]
- 325 x 390 x 160
- Type of surge arrester AC
- T2
- Type of surge arrester DC
- T1+2
- Residual current device
- Yes