SOL-407 T1+T2 2/1 R prefabricated DC Switchboard Iontec

SOL-407 DC T1+T2 2/1 R switchgear - 1 MPPT - surge arrester 1200 V

405.55excl. VAT

405.55 € incl. VAT
Zapytaj o cenę
SOL-407 T1+T2 2/1 R prefabricated DC Switchboard IontecSOL-407 T1+T2 2/1 R prefabricated DC Switchboard Iontec405.55 €

Your Query is sent.

  •     *Required Fields

Loading

.

The T1+T2 DC electrical switchgear provides full protection of DC circuits of a photovoltaic installation from the effects of surges. Its design is suitable for surface mounting.

The product consists of a housing, transparent door, TH-35 mm rails, N+PE terminals, front cover with cut-outs for apparatus, chokes, caps, and mounting parts.

Electrical and mechanical parameters of the enclosure:

  • Designed for surface mounting
  • Manufactured in accordance with EN 60670, EN 62208
  • Rated current In 63 A
  • IP65 rating
  • Protection class II
  • Rated insulation voltage Ui: 690 V AC, 1000 V DC
  • Glow wire test: 650°C
  • Impact resistance: IK08
  • Operating temperature: -25°C to +60°C
  • Halogen-free recyclable plastic

Isolating switch disconnector DC Noark Ex9IP 1000 V 32 A:

  • Manufactured in accordance with  IEC/EN 60947-3
  • Rated voltage: 1000 V
  • Rated current: 32 A
  • Size: 4 modules
  • Possibility to connect a surge or undervoltage tripping device

DC DEHN Combo 1200V typ 1+2 surge protector:

  • PV T1+T2 (Class I+II, Type 1+2, B+C)
  • To be used in accordance with the standard: PN-HD 60364-7-712
  • Rated discharge current In: 20 kA (8/20 μs)
  • Voltage protection level: 3.8 kV
  • Size: 4 modules
  • Maximum PV voltage Ucpv: 1200 V
  • Tripping time tA 25 ns
  • Optional auxiliary contact to indicate insert status
SOL-407

Attributes

Switchgear type
Prefabricated
Type of protection
DC
Max. voltage [V]
1000
Number of MPPT inputs
2
Switchboards
12-pole
Dimensions [mm]
325 x 390 x 160
Maximum current per one MPPT [A]
30
Type of surge arrester DC
T1+2
Number of strings
2