SOL- 610 T2 T2 1/1 prefabricated DC AC Consumer Units Iontec

SOL-610 DC T2 AC 1F 16 A T2 1/1 switchgear - 1 MPPT - surge arrester 1000 V

145.29excl. VAT

145.29 € incl. VAT
Zapytaj o cenę
SOL- 610 T2 T2 1/1 prefabricated DC AC Consumer Units IontecSOL- 610 T2 T2 1/1 prefabricated DC AC Consumer Units Iontec145.29 €

Your Query is sent.

  •     *Required Fields

Loading

.

The ACDC T2 T2 electrical switchgear provides full protection of DC circuits of a photovoltaic installation from the effects of surges. Its design is suitable for surface mounting.

The product consists of a housing, transparent door, TH-35 mm rails, N+PE terminals, front cover with cut-outs for apparatus, chokes, caps, and mounting parts.

Electrical and mechanical parameters of the enclosure:

  • Designed for surface mounting
  • Manufactured in accordance with EN 60670, EN 62208
  • Rated current In 63 A
  • IP65 rating
  • Protection class II
  • Rated insulation voltage Ui: 690 V AC, 1000 V DC
  • Glow wire test: 650°C
  • Impact resistance: IK08
  • Operating temperature: -25°C to +60°C
  • Halogen-free recyclable plastic

Overcurrent circuit breaker:

  • B curve
  • Manufactured in accordance with IEC/EN 60898-1
  • Rated short-circuit breaking capacity ICN: 6 kA
  • Rated switching voltage 230 V AC

NOARK Ex9UEP 20 3P 1000 V DC surge protector:

  • PV T2 (Class II, Type 2, C)
  • Designed in compliance with 50539-11
  • Rated discharge current In: 20 kA (8/20 μs)
  • Maximum discharge current Imax: 40 kA (8/20 μs)
  • Size: 3 modules
  • Rated switching voltage Un: 1,000 V
  • Thermal protection function
  • Optional auxiliary contact to indicate insert status

AC surge arrester:

  • T2 (Class II, Type 2, C)
  • Rated discharge current In (8/20 us) per phase: 20 kA
  • Continuous operating voltage Uc: 275 V per phase
  • Size: 2 modules
SOL-610

Attributes

Switchgear type
Prefabricated
Type of protection
DC/AC
Max. voltage [V]
1000
Max. current [A]
16
Feed-in phases
1
Number of MPPT inputs
1
Switchboards
12-pole
Dimensions [mm]
265 x 325 x 160
Type of surge arrester AC
T2
Type of surge arrester DC
T2
Number of strings
1
Residual current device
No