The BMV-702 is a high precision battery monitor. The essential function of a battery monitor is to calculate ampere hours consumed and the state of charge of a battery. Ampere hours consumed are calculated by integrating the current flowing in or out of the battery.
Midpoint voltage monitoring
This feature, which is often used in industry to monitor large and expensive battery banks, is now for the first time made available at a low cost, to monitor any battery bank.
A battery bank consists of a string of series connected cells. The midpoint voltage is the voltage halfway along the string. Ideally, the midpoint voltage would be exactly half of the total voltage. In practice, however, deviations will be seen, that depend on many factors such as a different state of charge for new batteries or cells, different temperatures, internal leakage currents, capacities and much more.
Large or increasing deviation of the midpoint voltage, points to improper battery care or a failed battery or cell. Corrective action following a midpoint voltage alarm can prevent severe damage to an expensive battery. Please consult the BMV manual for more information.
Easy to install
All electrical connections are to the quick connect PCB on the current shunt. The shunt connects to the monitor with a standard RJ12 telephone cable. Included: RJ 12 cable (10 m) and battery cable with fuse (2 m); no other components needed.
Also included are a separate front bezel for a square or round display appearance, a securing ring for the rear mounting and screws for the front mounting.
Standard features:
Battery voltage, current, power, ampere-hours consumed and state of charge
Remaining time at the current rate of discharge
Programmable visual and audible alarm
Programmable relay, to turn off non critical loads or to run a generator when needed
500 Amp quick connect shunt and connection kit
Shunt selection capability up to 10.000 Amps
VE.Direct communication port
Stores a wide range of historical events, which can be used to evaluate usage patterns and battery health
Wide input voltage range: 6,5 – 95V
High current measurement resolution: 10 mA (0,01A)
Low current consumption: 2,9Ah per month (4mA) @12V and 2,2Ah per month (3mA) @ 24V
In the Support tab, there is an instructional video on how to install the BMV-7XX series monitor and optimization of synchronization parameters.
Communication type: | VE.Direct, Bluetooth |
---|---|
Dimensions [mm]: | 0.0 x 0.0 x 0.0 |